 HTM 2030 Thermal Disinfection Temperature Bands 

Disinfection
Temperature (a)

Maximum Allowable
Temperature

Minimum Exposure
Time

65 DegC

70 DegC

10 Minutes

73 DegC

78 DegC

03 Minutes

80 DegC

85 DegC

60 Seconds

90 DegC

95 DegC

12 Seconds (b)

93 DegC (c)

98 DegC

10 Minutes


a) The disinfection temperature is measured at the surface to be disinfected.

b) The exposure time of 1 second (as specified in BS 2745 Part 1) is too short for reliable measurement and a minimum time of 12 seconds should be used.

c) This time/temperature relationship is only used for items known to be contaminated with large amounts of pathogenic organisms, for example in laboratories.